Answer first: To convert kVA to kW, multiply by the power factor: kW = kVA × power factor. At a power factor of 0.9, 100 kVA is 90 kW. One “unit” of electricity on an Indian bill is one kilowatt-hour (kWh) — one kilowatt used for one hour. An industrial bill usually charges for both: a demand charge on the peak load, often measured in kVA, and an energy charge on the units consumed, measured in kWh or, in a growing number of states, in kVAh. |
An industrial electricity bill mixes four or five different units on a single page, and they are easy to confuse. The transformer is rated in kVA, the machinery in kW, the contract in kVA, the consumption in units, and the solar plant in kWp or MW. Each of them measures something different, and the differences are where money is gained or lost.
This page explains each unit, how to convert between them, and where each one appears on a bill. It uses no tariff rates — those differ by state, category and year — only the structure that every industrial consumer will recognise.
|
Formula: kW = kVA × power factor. And the reverse, kw to kva: kVA = kW ÷ power factor. |
Power factor is a number between 0 and 1 that describes how much of the current flowing into a site does useful work. The Bureau of Energy Efficiency defines it as the “ratio between the active power (kW) and apparent power (kVA)”. At a power factor of 1, kVA and kW are the same. Below 1, the same kVA delivers fewer kW.
|
Apparent power |
kW at PF 1.0 |
kW at PF 0.95 |
kW at PF 0.9 |
kW at PF 0.8 |
|
100 kVA |
100 |
95 |
90 |
80 |
|
250 kVA |
250 |
237.5 |
225 |
200 |
|
500 kVA |
500 |
475 |
450 |
400 |
|
1,000 kVA |
1,000 |
950 |
900 |
800 |
Why 0.8 appears everywhere. Diesel generator sets are conventionally rated in kVA at a power factor of 0.8 — a 320 kVA set, for instance, is sold as 256 kW. That is a rating convention used by manufacturers, not the power factor of a typical factory. Most industrial sites run well above it, and most tariff orders set the power factor penalty threshold at around 0.9.
The Bureau of Energy Efficiency's energy-management guide gives the three definitions:
The network has to carry the kVA, not just the kW. That is why the utility cares about power factor, and why a site with a poor power factor draws more current, and more of the network's capacity, for the same useful work.
|
Definition — one unit of electricity: One unit is one kilowatt-hour (kWh): the energy used by a load of one kilowatt running for one hour. In the Bureau of Energy Efficiency's words: “If 1kW (1000 watts) of a electrical equipment is operated for 1 hour, it would consume 1 kWh of energy (1 unit of electricity).” |
The kwh meaning is the key to reading any bill: kW is a rate, kWh is a quantity. A 50 kW machine running for 8 hours uses 400 kWh, or 400 units. The kW figure tells you how hard the supply is working at any moment; the kWh figure tells you how much energy was delivered over time.
Larger quantities use the same ladder. The mw full form is megawatt, a thousand kilowatts:
|
Unit |
Equals |
Where you will see it |
|
kWh (one unit) |
1,000 watt-hours |
Every bill; energy is metered in kWh even where it is billed in kVAh |
|
MWh |
1,000 kWh |
Large contracts; renewable energy certificates (one certificate = 1 MWh) |
|
MU (million units) |
1,000,000 kWh = 1 GWh |
Annual consumption of large plants; state and utility reports |
|
BU (billion units) |
1,000 MU = 1 TWh |
National generation and demand statistics |
Multiply the capacity in kW by the hours it runs. For the mw to units conversion: units = MW × 1,000 × hours.
That second example is where most confusion about renewable capacity begins. A project's size in MW says nothing on its own about how many units it will deliver; the conversion needs the plant's capacity utilisation factor, which depends on the technology and the site.
Most high-tension industrial and commercial consumers in India pay a two-part tariff, set each year by their State Electricity Regulatory Commission in a tariff order. The structure, not the rates, is what repeats across states. For the institutions behind it, see how India's power sector is structured.
|
Bill line |
What it measures |
|
Contract demand |
The maximum load you have agreed with your distribution company that you may draw — usually stated in kVA. |
|
Recorded maximum demand |
The highest average load actually drawn in any one demand interval during the month — the Bureau of Energy Efficiency describes it as the “highest average kVA recorded during any one-demand interval within the month”. Maharashtra's tariff, for example, uses 30-minute intervals. |
|
Billing demand and demand charge |
The fixed or demand charge is levied per kVA (or per kW) on the billing demand — typically the higher of the recorded maximum demand and a set share of the contract demand. The share varies by state; one state's current order uses 90 per cent. |
|
Energy charge |
Levied per unit consumed. The unit is kWh in some states and kVAh in others. |
|
Power factor |
Shown on most bills. Under kWh billing, a surcharge or rebate may depend on it; under kVAh billing, it is already built into the units billed. |
|
Time-of-day energy |
Consumption split by time block where time-of-day tariffs apply, with each block priced differently. |
|
Load factor |
Some tariffs show it and reward a high one. |
Drawing more than your contract demand costs extra. Most tariff orders levy a higher rate, or a penalty, on demand recorded above the contracted level. For a growing site, the contract demand is worth reviewing before it is exceeded, not after.
Energy used to be billed almost everywhere in kWh, with a separate adjustment for power factor. A number of states have moved high-tension consumers to kVAh billing, which measures apparent energy instead. Maharashtra approved kvah billing for all high-tension categories from 1 April 2020; Haryana and Punjab are among the other states that bill some categories in kVAh.
The two are approximately linked: kVAh ≈ √(kWh² + kVArh²), or kWh divided by the average power factor. (Meters add up kVAh interval by interval, so a power factor that varies through the month pushes kVAh slightly higher than the formula.) When the power factor is 1, kVAh and kWh are equal. When it is lower, kVAh is higher.
|
Energy used (kWh) |
Power factor (assumed steady) |
Energy billed under kVAh |
|
1,00,000 |
1.00 |
1,00,000 |
|
1,00,000 |
0.95 |
about 1,05,300 |
|
1,00,000 |
0.90 |
about 1,11,100 |
|
1,00,000 |
0.85 |
about 1,17,600 |
That is the whole point of kVAh billing. In Maharashtra's tariff approval, the Commission described it as having “an inherent mechanism to incentivize or penalize consumers according to their PF”. Under kVAh, a poor power factor raises the number of units billed, so there is usually no separate penalty line. Maharashtra's Commission also set kVAh rates lower than it would have set under kWh billing, to reflect this.
Under kWh billing, the same outcome is reached with an explicit power factor penalty and, in some states, a rebate. One southern state's current order, for example, adds a surcharge for every 0.01 by which the power factor falls below 0.90.
Either way, the practical message is the same: improving power factor reduces the bill for the same useful work, usually through capacitor banks or automatic power factor correction equipment. It is one of the few bill lines a site can change without changing what it produces.
A site that adds renewable supply — rooftop solar, a captive plant or power bought through open access — needs to keep the units straight, because different lines of the bill respond differently.
Understood this way, the bill becomes a tool for ensuring reliable power while advancing climate commitments: the units show exactly where cleaner supply lowers cost and where it does not.
Multiply kVA by the power factor. At a power factor of 0.9, 500 kVA equals 450 kW. At 0.8, it equals 400 kW.
Only when the power factor is exactly 1. Otherwise 1 kVA is less than 1 kW of useful power — 0.9 kW at a power factor of 0.9, for example.
Divide kW by the power factor. A 90 kW load at a power factor of 0.9 needs 100 kVA of supply capacity.
One kilowatt-hour: one kilowatt used for one hour. A 100-watt bulb left on for 10 hours uses one unit.
It depends on how long it runs. 1 MW running for one hour uses 1,000 units; running all year, 8.76 million units. For a solar or wind plant, multiply by its capacity utilisation factor.
Billing energy in kilovolt-ampere-hours rather than kilowatt-hours. Because kVAh rises as power factor falls, it builds the power factor effect into the units billed instead of adding a separate penalty.
Because the network has to carry apparent power. A distribution company sizes its lines and transformers for kVA, so most high-tension contracts set and charge demand in kVA.
Megawatt: one thousand kilowatts, or one million watts. It measures capacity or load, not energy; energy is measured in megawatt-hours.